• Monitor for overcurrent or undercurrent
• Manual resetting and automatically resetting supported
• Wide power supply range from 12to 240 VAC/DC.
• Easy to set up with wiring diagrams on the side of product
• Strong anti-interference capability
1.Function | |
01 | Overcurrent (Manual resetting/Auto resetting) |
02 | Undercurrent (Manual resetting/Auto resetting) |
03 | Over & Under current (Manual resetting) |
04 | Over & Under current (Auto resetting) |
2.Current | |||
Current range | Current range | ||
A0.5 | AC0.05A-0.5A | D0.5 | DC 0.05A-0.5A |
A1 | AC 0.1A-1A | D1 | DC 0.1A-1A |
A2 | AC 0.2A-2A | D2 | DC 0.2A-2A |
A5 | AC 0.5A-5A | D5 | DC 0.5A-5A |
A8 | AC 0.8A-8A | D8 | DC 0.8A-8A |
A16 | AC 1.6A-16A | D16 | DC 1.6A-16A |
Supply voltage | |
A | AC230V |
D | DC24V |
W | AC/DC12-240V |
ASC18-01 | ASC18-02 | |
Input Terminal | A1-A2 | |
Voltage range | AC 230V/ DC24V / AC/DC 12-240V | |
Power consumption | AC 3.5VA/ DC 2.0W | |
Voltage tolerance | -15%~+10% | |
Supply indication | Green LED | |
Relay indication | Red LED | |
Time ranges | 0.1s-10s | |
Setting | Button | |
Setting deviation | 0.1% | |
Measurement accuracy | 5%/±0.1A | |
Temperature coefficient | 0.05%/℃, at=20℃ (0.05%/℉, =68℉) | |
Output conctact | 1*SPDT | |
Rated current | 1*16A | |
Mechanical life | 1*10⁷ | |
Electrical life | 1*10⁵ | |
Ambient Temperature | -20...+60℃ /-40...+85℃ | |
Mounting | DIN rail EN/IEC 60715 | |
IP Rating | IP20 | |
Stripping length | 7mm (0.28in) | |
Installed altitude | ≤2200m | |
Pollution level | 2 | |
Max cable size | AWG13-20 0.4N·m | |
Dimension | 90mm*18mm*64mm | |
Weight | about 90g | |
Standards | GB/T 14048.5,IEC60947-5-1,EN6812-1 |
*The above information is subject to change without further notice